INSULATING MATS FOR ELECTRICAL PURPOSES IS:15652-2006 (Latest)
Insulation Mat For Electrical Purpose
IS:15652/2006 (Latest)Application: Safety from electrical shock is required for workmen whether they are involved in electricity generation, transmission, distribution or its use. Poly Electro safe Mat are highly recommended for total safety of workmen from electrical shock when working in or around environment like-
High Voltage Panels,
Sub-station,
Power Transformer Rooms,
LT & HT Labs,
Near Bus bars,
Near Control Panels etc.
| VOLTAGE RATEINGS | ||||
| Class | Thickness | Grade KV | Proof voltage | B/Down voltage |
| A | 2.0 mm | 3.3 | 10KV/3 minutes | 30 KV |
| B | 2.5 mm | 11 | 22KV/3 minutes | 45 KV |
| C | 3.0 mm | 33 | 36KV/3 minutes | 65 KV |
Construction: Made from Highly Electrical resistant Elastomers, free from any insertions (includes rubbers, latex and Elastomeric compound that may be natural or synthetic or a mixture or a combination of both)
Surface: Upper surface of the mat is having small anti-skid aberration marks (rough surface, without edges) to avoid slippery effects and lower surface is plain.
Dimensions: Sizes are 1mtr x 2mtr or long length and thickness as per classification & designation
Color: Any Color but without Metallic Derivatives.
Working Temp: -10 to 55°C
TYPICAL FEATURES:-
Confirming IS: 15652/2006 (Latest), ISI marked.
High Die Electric Strength Up to 65 KV.
Insulation Resistance Up to 1494000 Mega Ohm.
Fire Retardant.
Good Mechanical Properties to with Stand Load and Movement of Breaker Trolleys and Associated Electrical Equipment including heavy foot traffic.
No Adverse Effect of Acids, Alkalis and Transformer Oil.
Manufactured Without Any Metallic Derivatives
Suitable For Both A.C & D.C Electrical Installations
Easy To Install, Can Be Pasted.
Water And Moisture Proof, Does Not Decay.
High Tensile Strength and Elongation Properties
Approved from reputed organizations like CRPI/ERDA.
| TECHNICAL SPECIFICATION IS:15652/2006 | ||||
| S No. | Characteristics | Standard Values | ||
| 1 | Thickness | 2.0mm | 2.5mm | 3mm |
| 2 | Tensile Strength(N/mm²) | 15 | 15 | 15 |
| 3 | Elongation (%) | 250 | 250 | 250 |
| 4 | Insulation Resistance with water at 500V | 1,000,000MO | 1,000,000MO | 1,000,000MO |
| 5 | Leakage Current at 11KV | 10mA | 10mA | 10mA |
| 6 | Dielectric Strength | 30KV | 45KV | 65KV |
| 7 | Flame Retardance | 5.0sec | 5.0sec | 5.0sec |
| 8 | Effect to Acid, Alkali, Transformer Oil Acid: Tensile Str.(N/mm²) Elog(%) |
% Change from Original Value | % Change from Original Value | % Change from Original Value |
| 9 | Alkali: Tensile Str.(N/mm²) Elog(%) Diesel: Tensile Str.(N/mm²) Elog(%) T.Oil: Tensile Str.(N/mm²) Elong.) |
Tensile Strength 20% Elongation 20% |
Tensile Strength 20% Elongation 20% |
Tensile Strength 20% Elongation 20% |
| 10 | Ageing Properties at70 ±1 (°C) for 168 hrs. Tensile Strength (Elongation %) |
% Change from Original Value T.S 25% |
% Change from Original Value T.S 25% |
% Change from Original Value T.S 25% |